HZ-3150Transformer DC Resistance TesterIntroductionDC resistance of the transformer will test the project of a transformer manufacturing semi-finished products,finished appearance test,installation,Website:http://www.electric-test.com, testing and transfer of power sector preventive trials , which can effectively find the transformer coil selection, welding, loose joints, missing stocks, disconnection and other manufacturing after the existence of hidden defects and running.Functions and Features●Large output current, wide measuring range, small size, light weight, simple operation●High test speed, high precision, retest good, strong anti-jamming capability●With perfect protection circuit, high reliability●With discharge audible alarm function, clear discharge instructions , to reduce misuseTechnical ParametersOutput currents 50A 25A 10A 5A 2.5AMeasure range 50A: 100υΩ~400Ω 25A: 250υΩ~800mΩ10A: 500υΩ~2Ω 5A: 1mΩ~4Ω2.5A: 2mΩ~8ΩResolution 0.1υΩ Accuracy (0.2%+2字)Dimensions 390mm×235mm×245mmInstrument weight 12kgConditions of UseAmbient temperature -10℃~50℃Humidity ≦85%RHPower Supply AC220V10%Power frequency 501Hz