MODEL |
IG3115CS 1-12KW Pure Sine wave Output Inverter |
1KW |
1.5KW |
2KW |
3KW |
4KW |
5KW |
6KW |
8KW |
10KW |
12KW |
Input Wave form |
Sine wave (utility or generator) |
Nominal Voltage |
230Vac (120Vac optional) |
Low voltage trip |
90v ±4% & 184v/154v ±4% |
Low voltage re engage |
100v ±4% & 194v/164v±4% |
High voltage trip |
140v ±4% & 253v ±4% |
High voltage re engage |
135v ±4% & 243v±4% |
Nominal Input Frequency |
50Hz/ 60Hz (auto detection) |
Frequency range |
47Hz~65Hz |
Output Wave form |
(Bypass mode)same as input |
Efficiency on line transfer mode |
≥95%+ |
Line transfer time |
10ms Typical |
Bypass without battery connected |
Yes |
Inverter specification/output |
Output wave form |
Pure sine wave |
Output continuos power watts |
1000 |
1500 |
2000 |
3000 |
4000 |
5000 |
6000 |
8000 |
10000 |
12000 |
Output continuos power VA |
1000 |
1500 |
2000 |
3000 |
4000 |
5000 |
6000 |
8000 |
10000 |
12000 |
Power factor |
0.9-1.0 |
Nominal Output Voltage rms |
230Vac (120Vac optional) |
Output Voltage regulation |
+/- 10%rms |
Output frequency |
50Hz ± 0.3Hz or 60Hz ± 0.3Hz |
Safety Certification |
>88% |
Surge ratings |
3000 |
4500 |
6000 |
9000 |
12000 |
15000 |
18000 |
24000 |
30000 |
36000 |
Short circuit protection |
Yes,fault after 1 secs |
Inverter specification/input |
Nominal input voltage |
12V/24V/48V |
96V |
Minimum start voltage |
10V/20V/40V |
80V |
Low battery alarm |
10.5V/21V/42V |
84V |
Low battery trip |
10V/20V/40V |
80V |
High voltage alarm |
16V/32V/64V |
128V |
Power saver |
Same switched on/off on remote |
Charger mode specification |
Output voltage |
Dependent on battery type |
Charge current |
0-85A MAX |
35A MAX |
45A MAX |
50A MAX |
Battery initial voltage for start up |
0-15.7v for 12v(*2 for 24v;*4 for 48v;*8 for 96v) |
Over charge protection shutdown |
15.7v for 12v(*2 for 24v;*4 for 48v;*8 for 96v) |
Charger curves(4stage constant curren) |
battery types |
4 step digital controlled progressive charge |
Battery type |
Fast V Fast V(*2 for 24v;*4 for 48v) |
Gel U.S.A |
14 13.7 |
A.G.M. 2 |
14.6 13.7 |
Sealed lead acid |
14.4 13.6 |
Gel euro |
14.4 13.8 |
Open lead acid |
14.8 13.3 |
Calcium |
15.1 13.6 |
De-sulphation |
15.5 for 4 hrs |
Remote control/RS232/USB |
Yes. Optional |