APPLICATION
BASIC INFORMATION
Code Name
KVV
Rated Voltage (Uo/U)
450/750V
Cable Structure
CU/PVC Insulation/PVC Sheathed
CONSTRUCTION
Conductor
Preferred Number of cores:
2,3,4,5,7,8,10,12,14,16,19,24,27,30,37,44,48,52,61
The conductors shall comply with the requirement given in IEC 60228 for class 1 or 2.
– class 1 for solid conductors;
– class 2 for stranded conductors.
Insulation
PVC(Polyvinyl Chloride) Type PVC/A according to IEC
Sheathed
PVC(Polyvinyl Chloride) Type PVC/ST1 according to IEC
Other special application cable can be provided upon requests:
Fire-resistant,Flame-retardant,Low-halogen,Non-halogen,Low-fume,Low-smoke,as well as acid-alkali-proof,High temperature resistant,Termite and Rodent resistant,Water proof series and so on.
CABLE STANDARDS
IEC60245,JB/T8735,GB/T5013,BS,DIN,ICEA up on request.
The electrical and dimensional properties of this product are measured by the Technical and Quality Assurance department at the JiangNan Cables laboratory. Cable performance in respect of conductor resistance, construction quality (workmanship), dimensional consistency, and other parameters are verified to published standards and approved product drawings. Conformance to RoHS (Restriction of the use of Hazardous Substances) is determined and confirmed.CHARACTERISTICS
Conductor temperature
Maximum conductor temperature in normal use: 70℃
Installation temperature
Ambient temperature under installation shall not be below 0℃
Max.temperature of conductor under short circuit
-(Max.Duration 5 sec.)
PVC Insulated:160℃
Preferred Permissible bending radius
For non-armoured PVC insulated cable not less than: 6 times of cable diameter