APPLICATION
CABLE STANDARDS
IEC60245,JB/T8735,GB/T5013,BS,DIN,ICEA up on request.
The electrical and dimensional properties of this product are measured by the Technical and Quality Assurance department at the JiangNan Cables laboratory. Cable performance in respect of conductor resistance, construction quality (workmanship), dimensional consistency, and other parameters are verified to published standards and approved product drawings. Conformance to RoHS (Restriction of the use of Hazardous Substances) is determined and confirmed.CHARACTERISTICS
Rated voltage Uo/U:
450/750V
Premissible Max.continous operating Conductor temperature
PVC Insulated:70℃ XLPE Insulated:90℃
Upon short circuit (Max.Duration time 5 seconds)The Max.temperature of conductor not higher than:
PVC insulated:160℃ XLPE insulated:250℃
Installation temperature
Ambient temperature under installation shall not be below 0℃
Preferred Permissible bending radius
For non-armoured PVC insulated cable not less than: PVC insulated is 6 times of cable diameter;XLPE insulated is 8 times of cable diameter
For armoured or copper tape screened cable not less than:12 times of cable diameter
For screened flexible cable not less than 6 times of cable diameter
Other Special Application
Fire-resistant,Flame-retardant,Low-halogen,Non-halogen,Low-fume,Low-smoke,as well as acid-alkali-proof,High temperature resistant,Termite and Rodent resistant,Water proof series and so on.