APPLICATION
(Low Smoke Zero Halogen)LSZH Copper Conductor XLPE Insulated Heavy Steel Wire Armoured Polyolefin Sheathed Power Cable.
This product is suitable for using in power distribution networks or fixed installations for industrial equipments with rated voltage up to and including 0.6/1KV.
CABLE STANDARDS
GB/T12706-2008,IEC,BS,ASTM and etc. upon request.
BASIC INFORMATION
Code Name
WDZ-YJY43
Rated Voltage (Uo/U)
0.6/1KV
Cable Structure
Copper Conductor/XLPE Insulation/Polyolefin Inner Sheath/Heavy Steel Wire Armoured/Polyolefin Outer Sheath
CONSTRUCTION
Conductor
Number of conductors:1,2,3,4,5,3+1,4+1
The conductors shall comply with the requirement given in IEC
Insulation
XLPE(Cross-linked Polyethylene) according to IEC
Armoured
Heavy Steel Wire
Sheath
Low Smoke Zero Halogen Polyolefin according to IEC
CHARACTERISTICS
Conductor temperature
Maximum conductor temperature in normal use: 90℃
Max.short-circuit temperature
Maximum shall not exceed 250℃(5s Max,Duration)
Installation temperature
Ambient temperature under installation shall not be below 0℃
Minimum bending radius
The bending radius of cable: (D-Diameter of cable)
————————————-≥15D